Unisafe air insulated metal enclosed switchgear is one of the main product series of air insulated metal enclosed switchgear of ABB Group. It originates from europe and has a design and production history of more than 30 years. Its main features are as follows:
• Global products with excellent performance
-Implement the unified product standards of ABB Group to ensure
that global products have the same excellent performance
• Rich global operation experience to meet different needs of customers
• Compact structure and high space utilization
-The main circuit adopts the design of uniform electric field and
composite insulation, which has small overall size and reduces the
civil engineering investment of users
• Perfect mechanical safety interlock
-It has perfect "five prevention" mechanical interlocking to prevent
misoperation of operators and improve safety level
• High quality material selection and high reliability
-VD4 vacuum circuit breaker is equipped as standard. ABB's well-known vacuum interrupter, cast pole of new generation insulating
material and operating mechanism with functional modular design
are adopted
• Resistance to internal fault arc class IAC AFLR
-High structural strength, resistance to internal fault arc 31.5kA/1s,
meeting IAC AFLR
• Environmentally friendly and reduce carbon emissions
-The production process of PT fixed sealing pole used in VD4 vacuum
circuit breaker has no three wastes, the carbon emission is only 40%
of that of epoxy resin pole, and the PT material is 100% recyclable
and degradable, which is environmentally friendly.
• ABB abilitytm intelligent solution realizes the functions of hidden danger early warning and equipment health management.
Techniacl Paramenters of Switchgear
| Item | Technical Parameter |
|---|---|
| Rated voltage | 12 kV |
| Rated insulation level | 42/75 kV |
| Rated main bus current | …4000 A |
| Rated branch bus current | …4000 A |
| Rated short time withstand current(4s) | …40 kA |
| Rated peak value withstand current | …100 kA |
| Arcing withstand current | …40 kA |
| Basic external dimensions' | |
| Height | 2160 mm |
| Width / Rated current |
600 mm / 1250 A 750 mm / 2000 A 1000 mm / 2500~4000 A |
| Depth | 1550 mm |